DSE335 Auto Transfer Switch Control Module

DSE335 Auto Transfer Switch Control Module

The DSE335 Automatic Transfer Switch Control Module has been expertly developed to monitor the voltage and frequency of an incoming AC supply from two different sources. These sources can be generator or mains (utility), or a combination of both. The control module monitors Source 1 (S1) and Source 2(S2). When a failure occurs a start command is issued to the inactive source to take over the load. The module will return the load to the mains (utility) as soon as this becomes available.


OVERALL SIZE

240 mm x 181 mm x 42 mm (9.4” x 7.1” x 1.6”)


MAXIMUM PANEL THICKNESS

8.0 mm (0.3”)


PRODUCT VARIANTS

0335-01 – 335 Auto Transfer Switch Control Module – 12/24 Volt DC Supply

PANEL CUTOUT SIZE

220 mm x 160 mm (8.7” x 6.3”)


WEIGHT

0.9kg

Key Features Key Benefits
Automatic switch over between supplies. Ensures there is no break in power when the changeover occurs.
Manual restore to S1. Allows flexible control of source inputs.
Configurable inputs/outputs (12/12). 6 configurable volt-free outputs & 6 configurable DC outputs. Provides multiple installation options.
Power monitoring (kW h, kV Ar, kV Ah, kV Ar h). Provides clear accurate power measurement information.
Source 1/source 2 control. Allows flexible control of source inputs.
Check sync feature. Ensures the smoothest possible transfer is achieved.
Integral PLC editor. Ensures additional applications are easily integrated into the system.
RS232 & RS485 communications (user selectable). Provides secure and simple off site monitoring. All ports are continuously active.
Rotary ATS configuration. Provides alternator breaker type control.
Compatible with DSE160 power supply. When no DC supply is available the DSE160 power supply connects to an AC power supply and then to the control module.
DSE Configuration Suite PC Software. Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Configurable event log (250). Provides access to historical alarms and operational status.

 

Additional Features
– Passive closed transition. – Load inhibit. – Multiple date & time scheduler. – Adjustable MODBUS interframe delay.
– 1 Amp & 5 Amp CT secondary support. – Multiple topology support. – USB connectivity. – DSEWebNet® compatibility.
– Phase rotation detection. – Configurable timers & alarms. – SMS messaging. – Ethernet communications (with DSE855).
– Start inhibit
– DSENet® expansion.
– Backed-up real time clock.
DC Supply OUTPUTS
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
OUTPUTS A & E
Normally closed volt-free output 8 A AC at 250 V AC
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
OUTPUTS B & F
Normally open volt-free output
8 A AC at 250 V AC
MAXIMUM OPERATING CURRENT
480 mA at 12 V, 360 mA at 24 V
OUTPUTS C & D
Changeover volt-free output
8 A AC at 250 V AC
MAXIMUM STANDBY CURRENT
126 mA at 12 V, 96 mA at 24 VS1
AUXILIARY OUTPUTS G,H,I,J,K & L
2 A DC at supply voltage

 

S1 S2
VOLTAGE RANGE
15 V to 333 V AC (L-N)
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
FREQUENCY RANGE
3.5 Hz to 75 Hz
ELECTRO-MAGNETIC COMPATIBILITY ELECTRICAL SAFETY TEMPERATURE
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

 

VIBRATION HUMIDITY
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

 

SHOCK DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60529
IP65 – Front of module when installed into the control panel with the optional sealing gasket.