DSE4610 Auto Start Control Module

DSE4610 Auto Start Control Module

The DSE4610 is a compact Auto Start Control Module that has been developed to provide an outstanding range of features within a compact enclosure.


OVERALL SIZE

140 mm x 113 mm x 43 mm (5.5” x 4.4” x 1.5”)


MAXIMUM PANEL THICKNESS

8.0 mm (0.3”)


PRODUCT VARIANTS

4610-03 – 4610 Auto Start Control Module (Mpu,Ct,Rtc)

PANEL CUTOUT SIZE

118 mm x 92 mm (4.6″ x 3.6″)


WEIGHT

0.26kg


Key Features Key Benefits
Large back-lit icon LCD display. Displays information to the operator in a clear and concise format.
3-phase generator sensing. Provides true generator sensing.
600 V ph-ph nominal system compatibility. Provides global flexibility.
Generator & load power monitoring (kW, kV A, kV Ar, pf). Provides clear accurate power measurement information.
Generator overload protection (kW). Provides engine overload protection.
Configurable inputs & outputs. Provides multiple installation options.
Configurable DC, volt-free and staged loading outputs. Provides multiple installation options.
Fuel & crank outputs. Provides controlled engine starting and stopping.
Magnetic pick-up speed sensing. Provides full monitoring flexibility.
Engine speed protection, engine hours counter, engine pre-heat, engine run-time scheduler, engine idle control for start/stop. Ensures the engine is fully monitored for improved operating performance.
Battery voltage monitoring. Ensures the battery maintains enough power at all times.
Configurable event log (50). Provides access to historical alarms and operational status.
DSE Configuration Suite PC Software. Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.

 

Additional Features
– Power save mode.
– Engine maintenance alarms (3).
– Alternative configuration.
DC Supply OUTPUTS
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
OUTPUT A (FUEL)
10 A short term, 5 A continuous, at supply voltage
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
OUTPUT B (START)
10 A short term, 5 A continuous,
at supply voltage
MAXIMUM OPERATING CURRENT
85 mA at 12 V, 96 mA at 24 V
AUXILIARY OUTPUTs C & D
2 A DC at supply voltage
MAXIMUM STANDBY CURRENT
51 mA at 12 V, 47 mA at 24 V
MAXIMUM SLEEP CURRENT
35 mA at 12 V, 32 mA at 24 V
MAXIMUM DEEP SLEEP CURRENT
10 uA at 12 V, 10 uA at 24 V

 

GENERATOR MAGNETIC PICK-UP
VOLTAGE RANGE
15 V to 415 V AC (Ph-N)
26 to 719 V AC (Ph – Ph)
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
3.5 Hz to 75 Hz
FREQUENCY RANGE
10,000 Hz (max)
ELECTRO-MAGNETIC COMPATIBILITY ELECTRICAL SAFETY TEMPERATURE
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

 

VIBRATION HUMIDITY
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

 

SHOCK DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60529
IP65 – Front of module when installed into the control panel with the optional sealing gasket.