The DSEE400 is a new exciting and easy to use engine controller. The DSEE400 has been designed to provide flexible control with built in monitoring and protection, to be installed in a multiple choice of environmental conditions.
The DSEE400 is compatible with both electronic and mechanical diesel engines. It is fully configurable for a wide range of applications such as engine driven pumps and compressors.
189 mm x 125 mm x 54 mm (7.5″ x 4.9″ x 2.1″)
E400-01 – E400 Engine Controller
148 mm x 112 mm (5.8″ x 4.4″)
007-850 – Deutsch connector A (DT16-18SA-k004), 18 way complete with pins.
007-851 – Deutsch connector C (DT16-18SC-K004), 18 way complete with pins.
007-852 – Set of 2 harnesses, a & C connectors, pre-wired, 1.2 m cables marked.
Key Features | Key Benefits |
---|---|
Configurable trip points. | Provides flexibility for setting the trip parameters to the required engine specifications or application requirements. |
Configurable nominal speed. | Allows accurate setting of the required running speed value. |
Trip points can be latching or non-latching. | Trips can lock the system out until reset by user intervention (latched), or reset on removal of the trip fault (non Latching). |
Analogue meter output. | Provides the option for visual speed indication. |
Potted electronics. | Prevents water ingress and vibration damage. |
Spade terminals. | Convenient and easy connections. |
DC Supply | OUTPUTS |
---|---|
CONTINUOUS VOLTAGE RATING 8 V to 35 V Continuous |
TRIP 1 & 2 16 A at 35 V DC/AC |
CRANKING DROPOUTS Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. |
TACHOMETER 1mA Full Scale |
MAXIMUM OPERATING CURRENT 95 mA at 12 V, 100 mA at 24 V |
|
MINIMUM OPERATING CURRENT 21 mA at 12 V, 22 mA at 24 V |
ALTERNATOR | MAGNETIC PICK UP |
---|---|
VOLTAGE RANGE 15 V – 333 V AC (L-N) RMS |
VOLTAGE RANGE +/- 0.7 V to 70 V RMS |
FREQUENCY RANGE 3.5 Hz to 75 Hz |
FREQUENCY RANGE 10,000 Hz (max) |
ELECTRO-MAGNETIC COMPATIBILITY | ELECTRICAL SAFETY | TEMPERATURE |
---|---|---|
BS EN 61000-6-2 EMC Generic Immunity Standard for the Industrial Environment. |
BS EN 60950 Safety of Information Technology Equipment, including Electrical Business Equipment. |
BS EN 60068-2-1 Ab/Ae Cold Test -30°C. |
BS EN 61000-6-4 EMC Generic Emission Standard for the Industrial Environment. |
BS EN 60068-2-2 Bb/Be Dry Heat +70°C. |
VIBRATION | HUMIDITY |
---|---|
BS EN 60068-2-6 Ten sweeps in each of three major axes. 5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn. |
BS EN 60068-2-30 Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours. |
BS EN 60068-2-78 Cab Damp Heat Static 40° C @ 93% RH 48 Hours. |
SHOCK | DEGREES OF PROTECTION PROVIDED BY ENCLOSURES |
---|---|
BS EN 60068-2-27 Three shocks in each of three major axes 15 gn in 11 ms. |
BS EN 60529 IP65 – Front of module when installed into the control panel with the optional sealing gasket. |