The DSEP100 detects and protects multiple devices that generate power in parallel with the mains (utility) supply. Examples include diesel generators, photovoltaic (solar) installations and wind turbine installations.
The DSEP100 ensures that all mains (utility) failures are detected. When detection takes place the mains (utility) supply is disconnected from the local source in line with international requirements. This removes the risk of power being supplied to an islanded grid.
157 mm x 95 mm x 67 mm (6.2” x 3.5” x 2.6”)
N/A
P100-01 – P100 Mains (Utility) Decoupling Relay
N/A
0.38kg
Key Features | Key Benefits |
---|---|
Detects mains (utility) failures when in parallel with another supply. | Eliminates the possibly of power being supplied into an islanded grid. |
R.O.C.O.F & vector shift. | Provides accurate & complete protection. |
Positive sequence over voltage/negative sequence under voltage. | Detects imbalances in the measured system. |
Zero sequence over voltage protection (NVD protection). | Detects neutral voltage displacement. |
Two-stage under & over voltage and frequency protection. | Covers short-term and long-term voltage disturbances. |
Lockable security tab to prevent configuration changes after commissioning. | Ensures the device remains tamper proof once installed. |
10 second rolling average over voltage protection. | Protects the device and connected equipment. |
World standard integration (G59/3, G83,3, C10/11, CEO 10-21). | Provides flexibility and choice in country and applications. |
Configurable event log (250). | Provides access to historical alarms and operational status. |
DSE Configuration Suite PC Software. | Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring. |
Additional Features |
---|
– Voltage asymmetry protection. | – Front panel/PC software configuration. | – Configurable volt free changeover relays (5). |
– Vector shift protection. | – SCADA monitoring. | – DIN rail mount. |
– Incorrect phase sequence protection. | – Alarm reset button. | |
– True 3-phase mains (utility) RMS measurement. |
DC Supply | AC POWER SUPPLY |
---|---|
CONTINUOUS VOLTAGE RATING 8 V to 35 V Continuous |
CONTINUOUS VOLTAGE RATING 85 V to 305 V AC (Ph to N) |
CRANKING DROPOUTS Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. |
CONTINUOUS FREQUENCY RATING 3.5 Hz to 75 Hz |
MAXIMUM OPERATING CURRENT 360 mA at 12 V, 170 mA at 24 V |
MAXIMUM OPERATING CURRENT 58 mA at 110 V AC (Ph to N) 28 mA at 230 V AC (Ph to N) |
MAINS (UTILITY) | OUTPUTS |
---|---|
VOLTAGE RANGE 15 V to 333 V AC (Ph to N) 26 V to 576 V AC (Ph to Ph) |
OUTPUT A, B, C, D & E Volt-Free Change-Over 5 A at 30 V DC 8 A at 250 V AC |
FREQUENCY RANGE 3.5 Hz to 75 Hz |
ELECTRO-MAGNETIC COMPATIBILITY | ELECTRICAL SAFETY | TEMPERATURE |
---|---|---|
BS EN 61000-6-2 EMC Generic Immunity Standard for the Industrial Environment. |
BS EN 60950 Safety of Information Technology Equipment, including Electrical Business Equipment. |
BS EN 60068-2-1 Ab/Ae Cold Test -30°C. |
BS EN 61000-6-4 EMC Generic Emission Standard for the Industrial Environment. |
BS EN 60068-2-2 Bb/Be Dry Heat +70°C. |
VIBRATION | HUMIDITY |
---|---|
BS EN 60068-2-6 Ten sweeps in each of three major axes. 5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn. |
BS EN 60068-2-30 Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours. |
BS EN 60068-2-78 Cab Damp Heat Static 40° C @ 93% RH 48 Hours. |
SHOCK | DEGREES OF PROTECTION PROVIDED BY ENCLOSURES |
---|---|
BS EN 60068-2-27 Three shocks in each of three major axes 15 gn in 11 ms. |
BS EN 60529 IP65 – Front of module when installed into the control panel with the optional sealing gasket. |