DSE7310 MKII Auto Start Control Module

DSE7310 MKII Auto Start Control Module


Project Description

The DSE7310 MKII is a powerful, new generation auto start genset control module with a highly sophisticated level of new features and functions, presented in the usual DSE user-friendly format. Suitable for a wide variety of single, diesel or gas Gen-set applications.

Featuring a new Dual Core main processor and extended memory, the module provides faster and more powerful processing power, returning faster operational responses on intensive applications and increased functionality, with data logging facility.

Monitoring an extensive number of engine parameters, the module will display warnings, shutdown and engine status information on the back-lit LCD screen, illuminated LED’s, remote PC’s and via SMS text alerts (with external communication device).

OVERALL SIZE
245 mm x 184 mm x 51 mm (9.6″ x 7.2″ x 2.0″)
MAXIMUM PANEL THICKNESS
8.0 mm (0.3″)
PANEL CUTOUT SIZE
220 mm x 160 mm (8.7″ x 6.3″)
PRODUCT VARIANTS
7310-03 – 7310 MKII Autostart Control Module
dse-genset-productscertified-icon1
Key Features Key Benefits
4-line back-lit LCD text display Provides comprehensive and clear indication of operation and parameters.
Five key menu navigation Provides convenient and flexible navigation of parameters
Support for up to three remote display units Provides the option to mimic the main control module up to 1.2 km
Configurable inputs (8) Provides multiple installation options.
Configurable analogue / digital inputs (6) Provides flexibility for multiple installation options.
Configurable outputs (8) Provides multiple installation options.
Tier 4 CAN engine support. Ensures the control module can be used with the latest in modern electronic engine technology.
Integral PLC editor. Ensures additional applications are easily integrated into the system.
Manual fuel pump control. Allows the fuel tank to be filled to provide reassurance of system operation
Power monitoring (kW h, kVAr, kv Ah, kV Ar h), reverse power protection, kW overload protection. Provides clear accurate power measurement information.
Configurable CT positioning. The CT can be placed in the Generator output to provide current readings and protection or alternatively placed in the main load output to provided generator and mains (utility) readings and protection.
Data logging facility Provides current and historical status information.
Customisable power up text and images Company logo can be uploaded to the start up splash screen.
Support for 0-10 V & 4-20mA oil pressure senders. Provides support for a wide range of sensors and parameters.

 

Additional Features
– Voltage measurement – Configurable timers & alarms – Charge alternator failure alarm
– kW overload alarms – Configurable start/stop timers – Speed control for speed control enabled electronic engines
– Exercise timer – Configurable maintenance alarms (3) – Heated Display option
– Multiple language options
DC Supply GENERATOR & MAINS (UTILITY) MAGNETIC PICK UP
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
5 V for up to 1 minute
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
25 V to 719 V AC (Ph to Ph)
VOLTAGE RANGE
+/- 0.5 V to 70 V
CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
FREQUENCY RANGE
3.5 Hz to 75 Hz
FREQUENCY RANGE10,000 Hz (max)
MAXIMUM OPERATING CURRENT
510 mA at 12 V, 240 mA at 24 V
MAXIMUM STANDBY CURRENT
330 mA at 12 V, 160 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
ELECTRO-MAGNETIC COMPATIBILITY ELECTRICAL SAFETY TEMPERATURE
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

 

VIBRATION HUMIDITY
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

 

SHOCK DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60529
IP65 – Front of module when installed into the control panel with the optional sealing gasket.