DSE890 DSEWebNet® Gateway – 3G (GSM)/Ethernet

DSE890 DSEWebNet® Gateway – 3G (GSM)/Ethernet


Project Description

The Gateway connects to the DSE data server by integral Ethernet connection or GPRS (DSM or 3G mobile internet) and includes GPS (satellite location) functionality. This is most suited to remote and/or mobile locations.

OVERALL SIZE
85 mm x 149 mm x 51 mm (3.4” x 5.9” x 2.0”)
PRODUCT VARIANTS
0890-01 – 890 DSEWebnet Gateway – 3G GSM/Ethernet
WEIGHT
0.25kg
dse-ast-productscertified-icon3
Key Features
Instant access to the full DSEWebNet® system.
DIN rail mount.
Multiple users can access each DSE891 simultaneously.
Communicates with connected DSE control modules via USB, Ethernet, RS232 or RS485.
DC Supply COMMUNICATIONS
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
USB (Single DSE Controller)
RS232 (Single DSE Controller)
RS485 (Multiple DSE Controllers)
Ethernet (Multiple DSE Controllers)
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
GSM : 700 mA at 12 V
: 450 mA at 24 V
GSM & GPS : 700 mA at 12 V
: 450 mA at 24 V
Ethernet : 200 mA at 12 V
: 110 mA at 24 V
Ethernet & GPS : 700 mA at 12 V
: 450 mA at 24 V
MAXIMUM STANDBY CURRENT
MAXIMUM STANDBY CURRENT
GSM : 270 mA at 12 V
: 150 mA at 24 V
GSM & GPS : 150 mA at 24 V
Ethernet : 150 mA at 12 V
:90 mA at 24 V
Ethernet & GPS : 270 mA at 12 V
: 150 mA at 24 V
ELECTRO-MAGNETIC COMPATIBILITY ELECTRICAL SAFETY TEMPERATURE
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

 

VIBRATION HUMIDITY
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

 

SHOCK DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60529
IP65 – Front of module when installed into the control panel with the optional sealing gasket.