DSE892 Simple Network Management Protocol (SNMP) Gateway

DSE892 Simple Network Management Protocol (SNMP) Gateway


Project Description

The DSE892 connects DSE control modules to external SNMP systems. Once a connection is made full monitoring and control functionality becomes active. The gateway device specialises in monitoring the instrumentation and operating state of the connected DSE control module.

The DSE2510 is a remote display module designed specifically for use with the DSE73xx control modules. A maximum of three remote display controls can be connected to a single host controller. The remote display can be located up to a maximum of 1km away.

OVERALL SIZE
85 mm x 149 mm x 51 mm (3.3” x 5.8” x 2.0”)
PRODUCT VARIANTS
0892-01 – 892 Simple Management Network Protocol (SMNP) Gateway
WEIGHT
0.24kg
dse-ast-productscertified-icon6
Key Features
Multiple DSE control module compatibility.
Communication port status LEDs.
DIN rail mount.
Plug & socket connections.
Auto generated Email/SNMP TRAP messages when control module events and operarting changes take place.
Customisable Email/SNMP TRAPs based upon module instrumentation values.
Simple Internet browser configuration.
SMTP client email.
Automatic MIB file generation to ease system integration.
Single DSE892 gateways can be connected to multiple control modules.
SNMP SET to change controller mode
SNMP GET for instrumentation
SNMP V2 compatibility
DC Supply COMMUNICATIONS
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
USB (Single DSE Controller)
RS232 (Single DSE Controller)
RS485 (Multiple DSE Controllers)
Ethernet (Multiple DSE Controllers)
Ethernet SNMP & SMTP
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 8 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
200 mA at 12 V
110 mA at 24 V
MAXIMUM STANDBY CURRENT
150 mA at 12 V
90 mA at 24 V
ELECTRO-MAGNETIC COMPATIBILITY ELECTRICAL SAFETY TEMPERATURE
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

 

VIBRATION HUMIDITY
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

 

SHOCK DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60529
IP65 – Front of module when installed into the control panel with the optional sealing gasket.