• WELCOME TO SARVAP SOLUTIONS PVT. LTD.
  • +0120-4917407, +91-9313543557
  •    
  • sales@sarvap.com

DSE3210 Manual & Auto Start Control Module

DSE3210 Manual & Auto Start Control Module

The DSE3210 is an outstanding compact control module that provides a comprehensive range of features for single-set applications. The controller can be used in manual or auto start mode.


OVERALL SIZE

98 mm x 79 mm x 40 mm (3.9” x 3.1” x 1.6”)


MAXIMUM PANEL THICKNESS

8.0 mm (0.3”)


PRODUCT VARIANTS

3210-01 – 3210 Manual & Auto Start Control Module (Mpu)

PANEL CUTOUT SIZE

80 mm x 68 mm (3.1 ” x 2.7″)


WEIGHT

0.18kg


Key Features Key Benefits
Front panel key switch. Ensures the generator can only be operated when the key is used.
Standard engine and electronic CANbus variants. Instant integration with both standard and modern electronically controlled engines.
Configurable inputs/outputs (6 digital inputs/4 outputs – 2 outputs configurable on magnetic pick-up variant). Provides multiple installation options.
Remote start input. Provides a simple connection to operate the generator from a remote location.
Comprehensive display parameters. Provides instant notification of generator voltage, generator frequency, battery voltage, engine speed and run hours via one button navigation.
Engine pre-heat Warms the engine to a safe temperature at start-up to increase engine life.
Configurable timers & alarms. Provides flexibility to suit individual operating requirements.
Large back-lit icon LCD display. Displays information to the operator in a clear and concise format.
DSE Configuration Suite PC Software. Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.

 

Additional Features
– LED & LCD alarm indications. – Shutdown warning protection for multiple fault conditions.
– Power save mode. – Tamper-proof hours counter.
– Configurable timers & alarms.
– Alternative configuration.
DC Supply OUTPUTS
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
OUTPUT A (FUEL)
2 A DC at supply voltage
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
OUTPUT B (START)
2 A DC at supply voltage
CHARGE FAIL/ EXCITATION
8 V to 35 V fixed power source 2.5 W
AUXILIARY OUTPUTs C & D
2 A DC at supply voltage
NOMINAL STANDBY CURRENT
35 mA at 12 V, 30 mA at 24 V
MAXIMUM OPERATING CURRENT
55 mA at 12 V, 60 mA at 24 V

 

GENERATOR MAGNETIC PICK-UP
VOLTAGE RANGE
15 V – 333 V AC (L-N)
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
3.5 Hz to 75 Hz
FREQUENCY RANGE
10,000 Hz (max)
ELECTRO-MAGNETIC COMPATIBILITY ELECTRICAL SAFETY TEMPERATURE
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

 

VIBRATION HUMIDITY
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

 

SHOCK DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60529
IP65 – Front of module when installed into the control panel with the optional sealing gasket.