The DSE701 MKII is a compact control module that offers a range of features for single-set applications. The controller can be used in manual or auto start mode.


OVERALL SIZE

72 mm x 72 mm x 38 mm (2.8” x 2.8” x 1.5”) Excludes Key Switch


MAXIMUM PANEL THICKNESS

8.0 mm (0.3”)


PRODUCT VARIANTS

0701-05 – 701MKII Manual & Auto Start Control Module

PANEL CUTOUT SIZE

68 mm x 68 mm (2.7 ” x 2.7″)


WEIGHT

0.14kg


Key Features Key Benefits
Front panel key switch. Ensures the generator can only be operated when the key is used.
Configurable for use as a manual or auto start control module. Helps to reduce module variants held in stock.
Auxiliary shutdown input (manual mode only). Provides a simple input for a remote stop switch.
LED status indication. Provides instant generator operating status.
Engine pre-heat. Warms the engine to a safe temperature at start-up to increase engine life.
Engine monitoring & protection. Protects engine from long-term damage.
Over speed protection. Prevents engines running too fast and becoming damaged.
DSE Configuration Suite Lite PC Software (DSE813 required). Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Monitors battery charging status using the WL terminal on the charge alternator. When the battery has a charging fault the module illuminates an LED on its front panel.
DC Supply OUTPUTS GENERATOR
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
START
Solid state 1.2 A negative grounding terminal
VOLTAGE RANGE
15 V – 333 V AC (L-N)
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
RUN
Solid state 1.2 A negative grounding terminal
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAXIMUN OPERATING CURRENT
26 mA at 12 V, 27 mA at 24 V
PRE-HEAT
Solid state 1.2 A negative grounding terminal
MAXIMUM STANDBY CURRENT
20 mA at 12 V, 21 mA at 24 V
CHARGE/FAIL EXITATION RANGE
0 V TO 35 V
ELECTRO-MAGNETIC COMPATIBILITY ELECTRICAL SAFETY TEMPERATURE
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

 

VIBRATION HUMIDITY
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

 

SHOCK DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60529
IP65 – Front of module when installed into the control panel with the optional sealing gasket.