The DSE701 MKII is a compact control module that offers a range of features for single-set applications. The controller can be used in manual or auto start mode.
72 mm x 72 mm x 38 mm (2.8” x 2.8” x 1.5”) Excludes Key Switch
8.0 mm (0.3”)
0701-05 – 701MKII Manual & Auto Start Control Module
68 mm x 68 mm (2.7 ” x 2.7″)
0.14kg
Key Features | Key Benefits |
---|---|
Front panel key switch. | Ensures the generator can only be operated when the key is used. |
Configurable for use as a manual or auto start control module. | Helps to reduce module variants held in stock. |
Auxiliary shutdown input (manual mode only). | Provides a simple input for a remote stop switch. |
LED status indication. | Provides instant generator operating status. |
Engine pre-heat. | Warms the engine to a safe temperature at start-up to increase engine life. |
Engine monitoring & protection. | Protects engine from long-term damage. |
Over speed protection. | Prevents engines running too fast and becoming damaged. |
DSE Configuration Suite Lite PC Software (DSE813 required). | Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring. |
Monitors battery charging status using the WL terminal on the charge alternator. | When the battery has a charging fault the module illuminates an LED on its front panel. |
DC Supply | OUTPUTS | GENERATOR |
---|---|---|
CONTINUOUS VOLTAGE RATING 8 V to 35 V Continuous |
START Solid state 1.2 A negative grounding terminal |
VOLTAGE RANGE 15 V – 333 V AC (L-N) |
CRANKING DROPOUTS Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. |
RUN Solid state 1.2 A negative grounding terminal |
FREQUENCY RANGE 3.5 Hz to 75 Hz |
MAXIMUN OPERATING CURRENT 26 mA at 12 V, 27 mA at 24 V |
PRE-HEAT Solid state 1.2 A negative grounding terminal |
|
MAXIMUM STANDBY CURRENT 20 mA at 12 V, 21 mA at 24 V |
||
CHARGE/FAIL EXITATION RANGE 0 V TO 35 V |
ELECTRO-MAGNETIC COMPATIBILITY | ELECTRICAL SAFETY | TEMPERATURE |
---|---|---|
BS EN 61000-6-2 EMC Generic Immunity Standard for the Industrial Environment. |
BS EN 60950 Safety of Information Technology Equipment, including Electrical Business Equipment. |
BS EN 60068-2-1 Ab/Ae Cold Test -30°C. |
BS EN 61000-6-4 EMC Generic Emission Standard for the Industrial Environment. |
BS EN 60068-2-2 Bb/Be Dry Heat +70°C. |
VIBRATION | HUMIDITY |
---|---|
BS EN 60068-2-6 Ten sweeps in each of three major axes. 5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn. |
BS EN 60068-2-30 Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours. |
BS EN 60068-2-78 Cab Damp Heat Static 40° C @ 93% RH 48 Hours. |
SHOCK | DEGREES OF PROTECTION PROVIDED BY ENCLOSURES |
---|---|
BS EN 60068-2-27 Three shocks in each of three major axes 15 gn in 11 ms. |
BS EN 60529 IP65 – Front of module when installed into the control panel with the optional sealing gasket. |