The DSE7210 is a feature packed Auto Start Control Module designed to control single diesel or gas gen-set applications.
240 mm x 181 mm x 42 mm (9.4” x 6.8” x 1.6”)
8.0 mm (0.3”)
7310-01 – 7310 Auto Start Control Module
7310-02 – 7310 Auto Start Control Module (Htr)
220 mm x 160 mm (8.7″ x 6.3″)
0.86kg
Key Features | Key Benefits |
---|---|
Heated display option. | Ensures the display continues to operate in extreme cold weather conditions. |
3-phase generator sensing. | Provides true generator sensing. |
Power monitoring (kW h, kV Ar, kV Ah, kV Ar h). | Provides clear accurate power measurement information. |
Remote communications (RS232 & RS485) | Provides secure and simple off site monitoring. All ports are continuously active. |
Configurable inputs/outputs (9/8). | Provides multiple installation options. |
CAN and magnetic pick-up sensing. | Makes the module ideal for standard and electronic engine applications. |
Fuel usage monitor and low level alarms. | Tracks the amount of fuel being used and sounds an alarm if over/under fuel use is detected. |
Tier 4 CAN engine support. | Ensures the control module can be used with the latest in modern electronic engine technology. |
True dual mutual standby with load balancing timer. | Enables two set systems to be configured to allow for redundancy or balancing run hours. |
Configurable display languages. | Ensures the control module is suitable for worldwide use. |
Power save mode. | Reduces the power usage within system batteries. |
Integral PLC editor. | Ensures additional applications are easily integrated into the system. |
Flexible sender inputs. | Allows alternative sender types to be selected using one input. |
DSE Configuration Suite PC Software. | Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring. |
Configurable event log (250). | Provides access to historical alarms and operational status. |
Load switching, load shedding & dummy load outputs. | Allows load options and dummy load requirements to be independently controlled. |
Additional Features |
---|
– Customisable status screens. | – Manual fuel pump control. | – Reverse power (kW & kV Ar) protection. | – Backed-up real time clock. |
– Multiple date & time scheduler. | – Engine exerciser. | – Unbalanced load protection. | – Configurable Gencomm pages. |
– Charge alternator failure alarm. | – kW & kV Ar overload protection. | – USB connectivity. | SMS messaging start & stop functionality. |
– CAN engine manual speed control. | |||
– Modem diagnostic display screens. | |||
– Remote display support (max 3 units). |
DC Supply | OUTPUTS |
---|---|
CONTINUOUS VOLTAGE RATING 8 V to 35 V Continuous |
OUTPUT A (FUEL) 15 A DC at supply voltage |
CRANKING DROPOUTS Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking. |
OUTPUT B (START) 15 A DC at supply voltage |
MAXIMUM OPERATING CURRENT 340 mA at 12 V, 160 mA at 24 V |
OUTPUTS C & D 8 A AC at 250 V AC (Volt free) |
MAXIMUM STANDBY CURRENT 160 mA at 12 V, 80 mA at 24 V |
AUXILIARY OUTPUTS E,F,G,H,I & J 2 A DC at supply voltage |
CHARGE FAIL/EXCITATION RANGE 0 V to 35 V |
GENERATOR | MAGNETIC PICK UP |
---|---|
VOLTAGE RANGE 15 V to 415 V AC (Ph to N) 26 V to 719 V AC (Ph to Ph) |
VOLTAGE RANGE +/- 0.5 V to 70 V |
FREQUENCY RANGE 3.5 Hz to 75 Hz |
FREQUENCY RANGE 10,000 Hz (max) |
ELECTRO-MAGNETIC COMPATIBILITY | ELECTRICAL SAFETY | TEMPERATURE |
---|---|---|
BS EN 61000-6-2 EMC Generic Immunity Standard for the Industrial Environment. |
BS EN 60950 Safety of Information Technology Equipment, including Electrical Business Equipment. |
BS EN 60068-2-1 Ab/Ae Cold Test -30°C. |
BS EN 61000-6-4 EMC Generic Emission Standard for the Industrial Environment. |
BS EN 60068-2-2 Bb/Be Dry Heat +70°C. |
VIBRATION | HUMIDITY |
---|---|
BS EN 60068-2-6 Ten sweeps in each of three major axes. 5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn. |
BS EN 60068-2-30 Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours. |
BS EN 60068-2-78 Cab Damp Heat Static 40° C @ 93% RH 48 Hours. |
SHOCK | DEGREES OF PROTECTION PROVIDED BY ENCLOSURES |
---|---|
BS EN 60068-2-27 Three shocks in each of three major axes 15 gn in 11 ms. |
BS EN 60529 IP65 – Front of module when installed into the control panel with the optional sealing gasket. |