DSE7210 Auto Start Control Module

DSE7210 Auto Start Control Module

The DSE7210 is a feature packed Auto Start Control Module designed to control single diesel or gas gen-set applications.


OVERALL SIZE

240 mm x 181 mm x 42 mm (9.4” x 6.8” x 1.6”)


MAXIMUM PANEL THICKNESS

8.0 mm (0.3”)


PRODUCT VARIANTS

7310-01 – 7310 Auto Start Control Module
7310-02 – 7310 Auto Start Control Module (Htr)

PANEL CUTOUT SIZE

220 mm x 160 mm (8.7″ x 6.3″)


WEIGHT

0.86kg


Key Features Key Benefits
Heated display option. Ensures the display continues to operate in extreme cold weather conditions.
3-phase generator sensing. Provides true generator sensing.
Power monitoring (kW h, kV Ar, kV Ah, kV Ar h). Provides clear accurate power measurement information.
Remote communications (RS232 & RS485) Provides secure and simple off site monitoring. All ports are continuously active.
Configurable inputs/outputs (9/8). Provides multiple installation options.
CAN and magnetic pick-up sensing. Makes the module ideal for standard and electronic engine applications.
Fuel usage monitor and low level alarms. Tracks the amount of fuel being used and sounds an alarm if over/under fuel use is detected.
Tier 4 CAN engine support. Ensures the control module can be used with the latest in modern electronic engine technology.
True dual mutual standby with load balancing timer. Enables two set systems to be configured to allow for redundancy or balancing run hours.
Configurable display languages. Ensures the control module is suitable for worldwide use.
Power save mode. Reduces the power usage within system batteries.
Integral PLC editor. Ensures additional applications are easily integrated into the system.
Flexible sender inputs. Allows alternative sender types to be selected using one input.
DSE Configuration Suite PC Software. Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Configurable event log (250). Provides access to historical alarms and operational status.
Load switching, load shedding & dummy load outputs. Allows load options and dummy load requirements to be independently controlled.

 

Additional Features
– Customisable status screens. – Manual fuel pump control. – Reverse power (kW & kV Ar) protection. – Backed-up real time clock.
– Multiple date & time scheduler. – Engine exerciser. – Unbalanced load protection. – Configurable Gencomm pages.
– Charge alternator failure alarm. – kW & kV Ar overload protection. – USB connectivity. SMS messaging start & stop functionality.
– CAN engine manual speed control.
– Modem diagnostic display screens.
– Remote display support (max 3 units).
DC Supply OUTPUTS
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
OUTPUT A (FUEL)
15 A DC at supply voltage
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
LEDs and backlight will not be maintained during cranking.
OUTPUT B (START)
15 A DC at supply voltage
MAXIMUM OPERATING CURRENT
340 mA at 12 V, 160 mA at 24 V
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
MAXIMUM STANDBY CURRENT
160 mA at 12 V, 80 mA at 24 V
AUXILIARY OUTPUTS E,F,G,H,I & J
2 A DC at supply voltage
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V

 

GENERATOR MAGNETIC PICK UP
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
3.5 Hz to 75 Hz
FREQUENCY RANGE
10,000 Hz (max)
ELECTRO-MAGNETIC COMPATIBILITY ELECTRICAL SAFETY TEMPERATURE
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

 

VIBRATION HUMIDITY
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

 

SHOCK DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60529
IP65 – Front of module when installed into the control panel with the optional sealing gasket.