The DSE2541 Remote Battery Charger Display Module has been designed to work with all intelligent and enclosed battery chargers. The module displays information to the operator on charge output, charge cycle, mains (utility) supply status and indicates when fault conditions are present.
The DSE2541 enables the user to control a battery charger remotely via the front panel buttons. The DSE2541 and its connected charger can be configured using the front panel buttons.
165 mm x 305 mm x 110 mm (6.5” x 12.0” x 4.3”)
8.0mm (0.3”)
2541-02 – 2541 Remote Battery Charger Display Module
118 mm x 92 mm (4.6” x 3.6”)
2.4kg
Key Features | Key Benefits |
---|---|
Large back-lit icon LCD display. | OProvides clear and easy to read information pages. |
Works with DSE94xx battery chargers. | Operates across the range of intelligent battery chargers. |
Front panel button charger configuration. | Makes programming quick and simple. |
LCD alarm indication. | Clear warning and indication to alert the user to an alarm. |
1 volt-free change over fault output. | Output provides the flexibility of the addition of an audible alarm. |
Remote battery charger & charge cycle monitoring. | Provides remote indication of the battery parameters and charging status. |
Remote boost and battery charger output control. | Provides user-friendly convenience of remote control of the charger, from a remote location. |
PC/laptop free configuration. | Quick and simple on-site set-up. |
DC SUPPLY |
---|
CONTINUOUS VOLTAGE RATING 8 V to 35 V Continuous |
CRANKING DROPOUTS Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking. |
MAXIMUM OPERATING CURRENT 80 mA at 12 V, 75 mA at 24 V |
MAXIMUM STANDBY CURRENT 65 mA at 12 V, 60 mA at 24 V |
FAULT OUTPUT |
---|
3 A at 30 V DC volt-free relay |
ELECTRO-MAGNETIC COMPATIBILITY | ELECTRICAL SAFETY | TEMPERATURE |
---|---|---|
BS EN 61000-6-2 EMC Generic Immunity Standard for the Industrial Environment. |
BS EN 60950 Safety of Information Technology Equipment, including Electrical Business Equipment. |
BS EN 60068-2-1 Ab/Ae Cold Test -30°C. |
BS EN 61000-6-4 EMC Generic Emission Standard for the Industrial Environment. |
BS EN 60068-2-2 Bb/Be Dry Heat +70°C. |
VIBRATION | HUMIDITY |
---|---|
BS EN 60068-2-6 Ten sweeps in each of three major axes. 5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn. |
BS EN 60068-2-30 Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours. |
BS EN 60068-2-78 Cab Damp Heat Static 40° C @ 93% RH 48 Hours. |
SHOCK | DEGREES OF PROTECTION PROVIDED BY ENCLOSURES |
---|---|
BS EN 60068-2-27 Three shocks in each of three major axes 15 gn in 11 ms. |
BS EN 60529 IP65 – Front of module when installed into the control panel with the optional sealing gasket. |