DSEA106 Auxiliary / Shunt Powered Digital AVR

DSEA106 Auxiliary / Shunt Powered Digital AVR

The DSEA106 Digital Automatic Voltage Regulator (AVR) is designed to regulate the output voltage of an AC alternator. The DSEA106 is supplied by either a stator auxiliary winding or a shunt system taking the power from the output windings.
The DSEA106 eliminates the complexities involved with analogue AVR designs. Analogue AVR designs can be over sensitive to changes in temperature which affects stability.


OVERALL SIZE

167 mm x 109 mm x 61 mm (6.6” x 4.3” x 2.4”)

PANEL CUTOUT SIZE

A106-01 – A106 Digital AVR (AUX)


Key Features Key Benefits
Digital electronic design. Ensures a smooth, stable, regulated AC output from the alternator.
Auxiliary or Shunt Power supplies. Suits a wide range of alternators.
Soft Start ramping. Helps to minimise voltage overshoot.
Loss of voltage sensing protection. Detects disconnection of the voltage sensing connections.
Quadrature CT connection. Suitable for synchronising and load sharing applications.
DIP Switch selection. Provides voltage, frequency and stability selection.
Potentiometer adjustment. Provides adjustments for voltage set points, droop, UFRO, proportional and integral gain.

 

Additional Features
– Remote voltage adjustment – Maximum current rating 15 A DC for 10 seconds.
– Compatible with all DSE synchronising and load sharing controllers. – Comprehensive protections, Under Frequency Roll Off (UFRO) protection, over excitation protection etc.
– Configuration using the DSE Configuration Suite PC Software, using the DSE814 interface. – An ideal option for both OEM and retro-fit solutions.
– LED Indication for fault and operating status.
POWER SUPPLY ALTERNATOR OUTPUT SENSING
VOLTAGE RANGE
100 V AC to 300 V AC (Ph to N/Ph)
VOLTAGE RANGE
15 V AC to 600 V AC (Ph to N/Ph)
FREQUENCY RANGE
40 Hz to 180 Hz
FREQUENCY RANGE
40 Hz to 65 Hz

 

EXCITATION OUTPUT QUADRATURE DROOP CT REMOTE VOLTAGE ADJUSTMENT
EXCITATOR FIELD WINDING IMPEDANCE
5 Ω to 50 Ω
MAXIMUM SECONDARY CURRENT
5 A AC
POTENTIOMETER
5 kΩ
CONTINUOUS VOLTAGE RATING
0 V DC to 100 V DC
BURDEN
0.25 VA
VOLTAGE INPUT
0 V DC to 10 V DC
CONTINUOUS CURRENT RATING
0 A DC to 7 A DC
ACCURACY
1%
MAXIMUM CURRENT RATING
15 A DC for 10 seconds
ELECTRO-MAGNETIC COMPATIBILITY ELECTRICAL SAFETY TEMPERATURE
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

 

VIBRATION HUMIDITY SHOCK
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.